The Schneider PM5100 is the ideal choice for cost management systems with CL0.5 kWh accuracy and a large back-lit LCD multilingual display
In a single 96 x 96 mm unit, with a graphical display, all three phases, neutral and ground can be monitored simultaneously.
The meters have direct connection up to 690V L-L without voltage transformers complaint with CAT III; allowing more free panel space for the user.
Product Specification
- Device(EM5100): Power monitoring
- Type of measurements: Active and reactive power (KVAR), Frequency (Hz), Power factor (0-1), Energy (W-KW), Voltage (V), Current (A)
- Supply voltage: 125-250 V DC or 110-415 V AC (45-65 Hz)
- Network frequency: 50 Hz - 60 Hz
- [In] rated current: 1 A, 5 A
- Type of network: 1P + Neutral, 3P (3Phase), 3P + Neutral
- Power consumption in VA:10 VA at 415 V
- Display type: Backlit LCD
- Display resolution:128 x 128 pixels
- Sampling rate:64 samples/cycle
- Measurement current:10 mA- 9 A
- Analogue input type: Voltage (impedance 5 MOhm)
- Current (impedance 0.3 mOhm)
- Measurement voltage: 20/400 V AC 45-65 Hz between phase and neutral 35/690 V AC 45-65 Hz between phases
- Frequency measurement range: 45-65 Hz
- Number of outputs: 1 digital
- Measurement accuracy: +/- 0.5 % voltage, +/- 0.5 % current, +/- 0.005 % power factor, +/- 0.05 % frequency, +/- 0.5 % apparent power, +/- 0.5 % active power, +/- 2 % reactive energy, +/- 0.5 % active energy
- Accuracy class: Class 0.5S (active energy according to IEC 62053-22)
- Insulation: 2500 V
- Data recording: Data logs, Event logs, Min/max of instantaneous values, Time, stamping, Alarm logs, Maintenance logs
- Memory capacity: 256 kB
- Mounting mode: Flush-mounted
- Mounting support: Framework
- Standards: IEC 60529, IEC 61557-12, IEC 62053-22, EN 50470-1, EN 50470-3, IEC 62053-24
- Width: 96 mm
- Depth: 72 mm
- Height: 96 mm
- Product weight: 430g